Wind-uplift test results.

A QDEK-bonded roof assembly, put through the roofing industry's wind-uplift test by an independent laboratory.

What the report says

Test method
ANSI/FM 4474 simulated wind-uplift test, 5 × 9 ft chamber, pressure increased in 15 psf steps and held 60 seconds at each step.
Tested assembly
50-mil FiberTite Fleeceback PVC over DensDeck and 2-inch polyiso on 22-gauge steel deck.
Adhesive name in the report
QDEK 3000 roofing adhesive; current product naming is UNO‑FOAM® | QD3000.
Result
The defined assembly met the 90 psf passing grade. Testing continued to 135 psf; the observed failure occurred at the cover-board facer, not at the QDEK adhesive bond.
Independent lab
PRI Construction Materials Technologies, ISO/IEC 17025-accredited.
Report
Report 2773T0002, issued May 30, 2025.
Availability
Full report available on request.

What it is

An independent third-party laboratory result for the specific assembly and test conditions listed above.

What it is not

It is not an FM Approval or listing, not a universal wind-uplift rating, not a guarantee for every roof assembly, and not a substitute for project-specific system approvals or design requirements.